BOLZTHERM® PW-60 is suitable for use in the liquid phase in closed, non-pressurized heat transfer systems with forced circulation in a temperature range of -50 °C to 240 °C. The maximum film temperature of 260 °C should not be exceeded. The optimal operating range is between 100 °C and 240 °C. For applications outside the optimal operating range, please contact us for consultation.
Typical characteristics | Unit | Standard | Value |
---|---|---|---|
Area of application | [°C] | - | -50 to 240 |
Max. flow temperature | [°C] | - | 240 |
Max. film temperature | [°C] | - | 260 |
Viscosity at 40 °C | [mm²/s] | DIN 51562-1 | 51.1 |
Viscosity at 100 °C | [mm²/s] | DIN 51562-1 | 9.67 |
Density at 20 °C | [kg/m³] | DIN 51757 | 1033 |
Pourpoint | [°C] | DIN ISO 3016 | <-50 |
Flash point | [°C] | DIN EN ISO 2719 | 220 |
Flash point | [°C] | DIN EN ISO 2592 | 260 |
Acid value | [mg KOH/g] | DIN ISO 6618 | ≤ 0.2 |
Coke residue | [w.-%] | DIN EN ISO 10370 | < 0.1 |
Boiling point at 1013 mbar | [°C] | - | >280 |